P/NO : MFL67798024
INSTALLATION MANUAL
AIR
CONDITIONER
www.lg.com
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
Original instruction
Copyright © 2015 - 2017 LG Electronics Inc. All Rights Reserved.
ENGLISH
FRANÇAIS
ESPAÑOL
1,MFL67798024,영어 2017. 9. 1. 오후 3:25 페이지 1
Vedere la pagina 0
1 2 3 4 5 6 ... 30 31

Sommario

Pagina 1 - CONDITIONER

P/NO : MFL67798024 INSTALLATION MANUALAIRCONDITIONERwww.lg.comPlease read this installation manual completely before installing the product.Installati

Pagina 2 - IMPORTANT SAFETY INSTRUC

10ENGLISH1 Always use the nitrogen.(not use oxygen, carbon dioxide, and aChevron gas): Please use the following nitrogen pressure0.02MPa(2.9psi) Oxyg

Pagina 3 - TABLE OF CONTENTS

11ENGLISHCAUTIONPlease block the pipe knock outs of the front and side panels afterinstalling the pipes. (Animals or foreign objects may be brought in

Pagina 4 - ALTERNATIVE REFRIGERANT R410A

12ENGLISH2 TonConnect the refrigerant pipe, and after the refrigerant leakage inspec-tion, cover with insulation material and wrap with vinyl tape.Tig

Pagina 5 - Air inlet grille

13ENGLISHTotal pipe length = A+B+C+D+a+b+c+d+e ≤ 300m(984ft)LLongest pipe length Equivalent pipe length(*)A+B+C+D+e ≤ 150m(492ft) A+B+C+D+e ≤ 175m(574

Pagina 6 - 3, 4, 4.4, 5 Ton

14ENGLISHWARNING• It is recommended that difference of piping length for pipesconnected to the Indoor Unit is minimized. Performance differ-ence betwe

Pagina 7 - Secure minimum intake area

15ENGLISHWARNING• Regulation for refrigerant leakage: the amount of refrigerant leakage should satisfy the followingequation for human safety.If the

Pagina 8 - INSTALLATION

16ENGLISH• When the number of indoor units to be connected to the branchpipes is less than the number of branch pipes available for connec-tion then c

Pagina 9 - Preparation of Piping

17ENGLISH[Unit:mm(inch)]Leak testLeak test should be made by pressurizing nitrogen gas to 3.8MPa(551.1psi). If the pressure does not drop for 24 hours

Pagina 10 - Moisture

18ENGLISHNOTE!Always add an appropriate amount of refrigerant. (For the refrigerant addi-tional charge) Too much or too little refrigerant will cause

Pagina 11 - INDOOR AND OUTDOOR UNIT

19ENGLISHABEBIABDC1m1mDFGBGDBHIJAⒶ SleeveⒷ Heat insulating materialⒸ LaggingⒹ Caulking materialⒺ BandⒻ Waterproofing layerⒼ Sleeve with edgeⒽ Lagging

Pagina 12

2ENGLISH• Do not cool excessively indoors. This may be harmful for your healthand may consume more electricity.• Block sunlight with blinds or curta

Pagina 13 - [Unit:m(ft)]

20ENGLISHSide panelWARNINGThe temperature sensor for outdoor air should not be exposed todirect sunlight.- Provide an appropriate cover to intercept d

Pagina 14 - 500mm(1.64ft)

21ENGLISH- Power supply cords of parts of appliances for outdoor use should notbe lighter than polychloroprene sheathed flexible cord.- Don't ins

Pagina 15 - Refrigerant charging

• Initial display order• Example) ARUN060GSS4Order No Note①4~12 Model capacity②1 Cooling only2 Heat pump③38 380V46 460V22 220V④1 Standard5 Cold temper

Pagina 16 - Y branch pipe

23ENGLISHExample) Group number setting 1stnumber indicate the group number2nd number point out indoor unit numberSODU.B SODU.A IDU.B IDU.A CEN.B CEN.A

Pagina 17 - Leak Test and Vacuum drying

24ENGLISHMaster unit PCB DIP switch on : No.5Select the mode using ‘▶’, ‘◀’ Button :“Func” Push the ‘●’ buttonSelect the Function using ‘▶’, ‘◀’ Butto

Pagina 18 - Vacuum Mode

25ENGLISHCAUTION• Ask an authorized technician to setting a function.• If do not use a function, set an off-mode.!Master unit PCB DIP switch on : No.5

Pagina 19 - ELECTRICAL WIRING

26ENGLISHError No. of CompressorError No.Error No. of UnitRepeatDisplay Title Cause of ErrorIndoor unit related error0 1 -Air temperature sensor of in

Pagina 20 - Side panel

27ENGLISHDisplay Title Cause of Error5 0 1Omitting connection of R, S, T power of Outdoor Unit Omitting connection of outdoor unit5 1 1Excessive capac

Pagina 21 - Field Wiring

Calculate minimum room capacityCalculate room capacity by regarding a portion as one room or thesmaller room.- With partition and with openingwhich se

Pagina 22 - Automatic Addressing

29ENGLISHCAUTION• Air conditioners should not be installed in areas wherecorrosive gases, such as acid or alkaline gas, are produced.• Do not install

Pagina 23 - B(D) A(C)

3CAUTIONInstallation• Always check for gas (refrigerant) leakage after installation or repair of product.- Low refrigerant levels may cause failure of

Pagina 24

30ENGLISH1,MFL67798024,영어 2017. 9. 1. 오후 3:26 페이지 30

Pagina 25 - Base Pan Heater setting

US1. Please call the installing contractor of your product, as warranty service will be provided by them.2. If you have service issues that have not b

Pagina 26 - Error No. of Unit

4ENGLISHThe foundation must be level evenOutdoor unit foundation workAvoid short circuits and ensure sufficient space is allowed for serviceInstallatio

Pagina 27

5ENGLISHAir inlet grille700[Unit : mm]Turn the air outlet side toward thebuilding's wall, fence or windbreak screen.WARNINGFix the outdoor unit f

Pagina 28 - CAUTION FOR REFRIGERANT LEAK

6ENGLISHIn case of obstacles on the discharge side1. Stand alone installation500(19-5/8) or more500(19-5/8) or less1000 (39-1/4) or more500(19-5/8) or

Pagina 29 - Product information

7ENGLISHSeasonal wind and cautions in winter• Sufficient measures are required in a snow area or severe cold areain winter so that product can be oper

Pagina 30

8ENGLISH• Fix the unit tightly with bolts as shown below so that unit will not falldown due to earthquake or gust.• Use the H-beam support as a base s

Pagina 31

9ENGLISHFlaring work- Carry out flaring work using flaring tool as shown below.Firmly hold copper tube in a bar(or die) as indicated dimension in thet