INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
ƓThis product contains Fluorinated Greenhouse Gases. (R410A)
TYPE : MULTI
Original instruction
P/NO : MFL67855417
ENGLISH
PORTUGUESE
MAGYAR
БЪЛГАРСKN
SRPSKI
HRVATSKI
SVENDKA NORSK SUOMI DANSK
ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
Vedere la pagina 0
1 2 3 4 5 6 ... 46 47

Sommario

Pagina 1 - AIR CONDITIONER

www.lg.comINSTALLATION MANUALAIR CONDITIONER • Please read this installation manual completely before installing the product.• Installation work must

Pagina 2 - TIPS FOR SAVING ENERGY

10INSTALLATION OF INDOOR, OUTDOOR UNITENGLISHPiping length and elevationMultiple Piping Models (Unit: m)Distributor type Models (Unit: m)Phase Capacit

Pagina 3 - IMPORTANT SAFETY INSTRUCTIONS

INSTALLATION OF INDOOR, OUTDOOR UNIT11ENGLISHRefrigerant chargeThe calculation of the additional charge should be taken in account for the length of e

Pagina 4 - Operation

12INSTALLATION OF INDOOR, OUTDOOR UNITENGLISHPreparing work for Installation (ART COOL Type Only)1 First, push the front panel backward and lift it up

Pagina 5

INSTALLATION OF INDOOR, OUTDOOR UNIT13ENGLISHSticking the installation guide map and fixing Indoor unit (ART COOL Type Only)Put an Installation Guide M

Pagina 6 - TABLE OF CONTENTS

14INSTALLATION OF INDOOR, OUTDOOR UNITENGLISHDrill the piercing part for connecting pipe as diameter Ø65mm. (In case of piercing rear surface)First, D

Pagina 7 - Installation Tools

INSTALLATION OF WIRED REMOTE CONTROLLER15ENGLISH1 Please fix tightly using provided screw after placing remote controller setup board on theplace wher

Pagina 8 - Select the best location

16INSTALLATION OF WIRED REMOTE CONTROLLERENGLISH4 Please connect indoor unit and remote controller using connection cable.5 Please use extension cable

Pagina 9 - Fixing Installation Plate

INSTALLATION OF WIRED REMOTE CONTROLLER17ENGLISH5feet(1.5meters)nononoyesFig.1 Typical locations for remote controllerWired remote controller installa

Pagina 10 - Piping length and elevation

18FLARING WORK AND CONNECTION OF PIPINGENGLISHFlaring workMain cause for gas leakage is due to defect in flaring work. Carry out correct flaring work

Pagina 11 - Refrigerant charge

FLARING WORK AND CONNECTION OF PIPING19ENGLISHCheck- Compare the flared work with figure below.- If flare is noted to be defective, cut off the flared

Pagina 12 - Drain hose junction

2TIPS FOR SAVING ENERGYENGLISH• Do not cool excessively indoors. This may be harmful to your health and may consume more elec-tricity.• Block sunlig

Pagina 13 - Horizontality

20FLARING WORK AND CONNECTION OF PIPINGENGLISHIndoor unit installationHook the indoor unit onto the upper portion ofthe installation plate.(Engage the

Pagina 14 - INSTALLATION GU

FLARING WORK AND CONNECTION OF PIPING21ENGLISH- Bundle the piping and drain hose together bywrapping them with vinyl tape over therange within which t

Pagina 15 - REMOTE CONTROLLER

22FLARING WORK AND CONNECTION OF PIPINGENGLISH- For the units with capacity more than 48kBtu/h, the installation piping is connectablein four directio

Pagina 16

FLARING WORK AND CONNECTION OF PIPING23ENGLISHY branchA B Facing upwardsViewed from point Ain direction of arrowHorizontalplaneWithin +/- 10°ALiquid a

Pagina 17 - (1.5meters)

24FLARING WORK AND CONNECTION OF PIPINGENGLISHInstallation- This unit may be installed suspended from the ceiling or mounted on the wall.- This unit m

Pagina 18 - Flaring work

FLARING WORK AND CONNECTION OF PIPING25ENGLISH((1) Ceiling-suspended type(2) Wall-mountde typeProcedure1 Fix the furnished hanger metal with twoscrews

Pagina 19 - Connection of piping - Indoor

26CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNITENGLISHConnect the cable to the Indoor unitConnect the cable to the indoor unit by connecti

Pagina 20

CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT27ENGLISHThe power cord connected to the outdoor unit should be complied with the following s

Pagina 21 - Ø12.7(1/2 inch) Connector

28CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNITENGLISH1 Remove the cover control from the unit byloosening the screw.Connect the wires t

Pagina 22 - <Figure 3>

CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT29ENGLISHUse round pressure terminals for connections to the power terminal block.When none a

Pagina 23

IMPORTANT SAFETY INSTRUCTIONS3ENGLISHIMPORTANT SAFETY INSTRUCTIONSREAD ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.Always comply with the following pr

Pagina 24 - Installation

30CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNITENGLISHConnection of Wiring- Connect refrigerant pipes and connectionwires to the appropria

Pagina 25 - Installation of The Main Unit

CHECKING THE DRAINAGE AND FORMING THE PIPINGS31ENGLISHChecking the DrainageTo check the drainage.1 Pour a glass of water on the evaporator.2 Ensure th

Pagina 26 - UNIT AND OUTDOOR UNIT

32CHECKING THE DRAINAGE AND FORMING THE PIPINGSENGLISHForming the PipingForm the piping by wrapping the connectingportion of the indoor unit with insu

Pagina 27 - AREA 0.75mm

AIR PURGING AND EVACUATION33ENGLISHCheck that each tube(both liquid and gas sidetubes) between the indoor and outdoor unitshave been properly connecte

Pagina 28

34AIR PURGING AND EVACUATIONENGLISH- When the desired vacuum is reached, closethe "Lo" knob of the manifold valve and stopthe vacuum pump.Re

Pagina 29

PANEL FRONT ASSEMBLY (ART COOL TYPE ONLY)35ENGLISH1 First, Check the side cover assemblyexactly, Fix power cord in the bottomgroove of cover side left

Pagina 30 - Connection of Wiring

36INSTALLATION PI485ENGLISHFix the PI485 PCB as shown in Fig.Detailed installation method refer to PI485 Installation Manual. 18k Btu/h, 21k Btu/h24kB

Pagina 31 - Drain piping

TEST RUNNING37ENGLISHRemove the battery cover by pulling it accord-ing to the arrow direction.Insert new batteries making sure that the (+)and (–) of

Pagina 32 - Forming the Piping

38FUNCTIONENGLISHDip S/W SettingIf you set the Dip Switch when power is on, the change in setting is notapplicable. The changing setting is enabled on

Pagina 33 - Leakage test

FUNCTION39ENGLISH14/16/18/21(1Ø) kBtu/h 40/48/56(1Ø) kBtu/h42/48/56(3Ø) kBtu/h24/27/30(1Ø) kBtu/hDIP-SWSW01NDIP SW2Forced Cooling OperationAdding the

Pagina 34 - Finishing the Job

4IMPORTANT SAFETY INSTRUCTIONSENGLISH• Safely dispose off the packing materials. Like screws, nails, batteries, broken things etc afterinstallation or

Pagina 35 - Connector

40FUNCTIONENGLISHSaving Power ConsumptionSaving Power Consumption operation is thefunction which enables efficient operation bylowering the maximum po

Pagina 36 - INSTALLATION PI485

FUNCTION41ENGLISHSaving Power Consumption Current level.Night Quiet ModeNight Quiet Mode operation lowers the noise level of the outdoor unit by chan

Pagina 37 - TEST RUNNING

42FUNCTIONENGLISHMode LockSetting Procedure1 Set the Dip Switch as follow after shutting the power source down.2 Reset the power.Mode Lock with Night

Pagina 38 - FUNCTION

FUNCTION43ENGLISHPCB Display(14/16/18/21k Model Only)It is useful to check the cycle data without LGMV.Whenever you push the Tact Switch, the cycle in

Pagina 39 - Forced Cooling Operation

44MAX COMBINATION CAPACITYENGLISHMulti Piping TypeDistributor TypeThe combination of indoor unit is to be decided that the sum of indoor unit capacit

Pagina 40 - Wiring Error Check

INSTALLATION GUIDE AT THE SEASIDE45ENGLISHIf the outdoor unit is to be installed close tothe seaside, direct exposure to the sea windshould be avoided

Pagina 41 - Night Quiet Mode

46SEASONAL WIND AND CAUTIONS IN WINTERENGLISHModel Designation Indoor unitOutdoor unitAirborne Noise EmissionThe A-weighted sound pressure emitted byt

Pagina 42 - Mode Lock

[Representative] LG Electronics Inc. EU Representative Krijgsman 1, 1186 DM Amstelveen, The Netherlands[Manufacturer] LG Electronics Inc. Changwon 2nd

Pagina 43 - Operating Method

IMPORTANT SAFETY INSTRUCTIONS5ENGLISH• Always check for gas (refrigerant) leakage after installation or repair of product. Low refrigerant lev-els may

Pagina 44 - MAX COMBINATION CAPACITY

6TABLE OF CONTENTSENGLISH2 TIPS FOR SAVING ENERGY3 IMPORTANT SAFETYINSTRUCTIONS7 INSTALLATION8 INSTALLATION OFINDOOR, OUTDOORUNIT8 Select the best loc

Pagina 45 - AT THE SEASIDE

INSTALLATION7ENGLISHInstallation plateType "B" screwsType "A" screw (6 EA) Type "A" screw (8 EA) Type "A" scre

Pagina 46 - Outdoor unit

8INSTALLATION OF INDOOR, OUTDOOR UNITENGLISHRead completely, then follow step by step.You need to select adequate installation locationconsidering the

Pagina 47

INSTALLATION OF INDOOR, OUTDOOR UNIT9ENGLISHFixing Installation PlateThe wall you select should be strong and solidenough to prevent vibration1 Mount